Updated IT security, OT security, Incident response
PSA: Take commercial refrigeration controllers off the public internet
Attacks on refrigeration systems in Bavaria and Europe: setpoints and defrost cycles were changed remotely. Three Danfoss AK-SM 800A flaws have been in CISA’s KEV catalog since 25 November. Remove internet exposure, check firmware, and apply the CERT-FR and ENISA guidance.

As of November 26, 2026, 8:00 a.m. CET. On 25 November CISA added three flaws in the Danfoss AK-SM 800A controller to its KEV catalog (catalog version 2026.11.25): CVE-2025-41450 (improper authentication, due 9 December) as well as CVE-2023-25914 (path traversal) and CVE-2023-25915 (command execution), both due 28 November. The listing is evidence of active exploitation. It is not evidence that these exact flaws were used in the October and November waves in France and Bavaria. Whether ransomware groups use them is recorded by CISA as unknown. For the two 2023 flaws, CISA requires US federal agencies to perform a forensic review. CVE-2025-41451 and the Copeland XWEB flaws CVE-2026-25085 and CVE-2026-21718 are still not in KEV. The specific entry paths of the current incidents have not been publicly established in full. Authorities have not attributed the attacks.
On the night of 1 to 2 November 2026, setpoints and operating modes of commercial refrigeration systems in Bavaria were changed remotely. At the Pflugsmühle restaurant in the district of Roth, the setpoint reached 150 degrees Celsius according to the operator and police statements; spoiled food caused about 5,000 euros in damage, and the Schwabach criminal investigation department is investigating (Nordbayern, Donaukurier/dpa). In the district of Neustadt an der Waldnaab (Upper Palatinate), police reported a comparable manipulation of cold stores at a butcher’s shop, with damage in the five-figure range (Onetz, tagesschau). In Reisbach in Lower Bavaria, operator Edeka Ernst found refrigeration units switched to “50 degrees heating”; large quantities of goods had to be discarded. The Niederbayern police headquarters confirmed unauthorized remote access, and the Landshut criminal investigation department is investigating (BR24, PNP).
If you run IT or security for retail, hospitality, production or healthcare, comparable controllers often sit outside your asset inventory: at the refrigeration contractor, behind their own router, with a web interface for remote maintenance. That interface is what sets temperatures, defrost cycles and alarms. Anyone who can reach it can often cause the damage that has been observed simply by using the controller’s intended operating functions.
A setpoint of 150 degrees does not mean the cold store physically reached that temperature. It is the manipulated target. Spoiled goods often need only a few hours without refrigeration. In several cases, operators also report that the usual alarms did not fire or that they were locked out of the software.
What came first in Europe
As early as the night of 11 to 12 October 2026, refrigeration systems at hundreds of French supermarkets were affected, including branches of Carrefour, Intermarché and E.Leclerc (Claroty). CERT-FR reported numerous compromises of Danfoss AK-SM and AK-SC as well as Copeland/Dixell XWEB units and advises against operating management interfaces on the public internet. Agency reports at the time cited ranges of several hundred affected stores; the exact figures differ by source.
On 1 and 2 November another wave followed in several EU countries, including Belgium, Sweden and the Netherlands. On 4 November the European Commission, ENISA and Europol EC3, together with the EU CSIRT network and EU-CyCLONe, published a warning: organizations should immediately reduce the exposure of affected systems. The statement does not attribute the attacks.
Richard Horne, head of the UK NCSC, publicly described the French incidents as involving older refrigeration controllers connected directly to the internet, some of them using default passwords (Computer Weekly).
What sits behind the refrigerated counter
Commercial installations gather many refrigerated points through a central system manager. Well-known platforms are Danfoss AK-SM (for example the AK-SM 800A) and Copeland XWEB Pro (Dixell brand). The web interface allows setpoints, time programs, alarms and maintenance. Downstream controllers often speak over serial buses such as Modbus. Successful access to the manager can affect many points at once.
Claroty Team82 examined such managers in physical test setups and showed that a compromised supervisor can control cooling, fans, lighting and defrost on attached controllers (Copeland research). Team82 also counted about 2,765 publicly reachable Danfoss AK-SM 800A interfaces (Claroty on the France incident).
We keep two points separate: public reachability explains how attackers find devices. Whether they logged in with a default password, a known firmware flaw or a service-provider account has not been publicly established across the European incidents.
Known vulnerabilities in Danfoss and Copeland controllers
For Danfoss AK-SM 8xxA, Claroty describes under CVE-2025-41450 an alternative authentication path (“Code of the Day”) derived from the device clock; Danfoss fixed this from firmware R4.2 (DSA-2025-03-01, NVD). CVE-2025-41451 is a command injection through alarm-mail configuration fields after a successful login; the fix starts at 4.3.1 (DSA-2025-08-01). Practical target: at least 4.3.1.
Since 25 November, CVE-2025-41450 and the older flaws CVE-2023-25914 and CVE-2023-25915 have been in the KEV catalog. CISA added them on the basis of evidence of active exploitation (alert of 25 November). Danfoss fixed the two 2023 flaws from firmware 3.3 (DSA-2023-08-01); CVE-2025-41450 is closed from 4.2. The practical target remains at least 4.3.1, so that CVE-2025-41451 is closed as well. The KEV listing does not say whether these flaws were used in the incidents in France and Bavaria.
For Copeland XWEB Pro, Team82 lists 23 vulnerabilities. CVE-2026-25085 is an authentication bypass in the Lua middleware (NVD). CVE-2026-21718 concerns predictable administrative credentials derived from device information and hardcoded keys. Copeland provides firmware 1.13. Whether the October and November attacks used the flaws now in KEV or the other CVEs named here has not been shown; default passwords and exposed interfaces are enough for many of the manipulations that were observed.
Why systems can “heat”
Many systems run defrost cycles with electric heaters or hot gas. The controller sets start time, duration and limits. Unauthorized configuration changes can interrupt cooling or leave defrost permanently active without destroying the hardware. The situation becomes critical when alarms run through the same controller and are switched off or bypassed.
Blood donation and the service-provider chain
On the night of 1 to 2 November, controllers for cold rooms of the Établissement français du sang were manipulated at three sites. The EFS reports no loss of blood products; the health ministry describes the situation as under control. The service provider affected was Coolworld Rentals (La RPF). On 4 November Coolworld confirmed an incident and pointed to a third-party component in the remote-monitoring software (Coolworld). Independent temperature sensors and separate alarm paths limit the damage when the central controller is no longer trustworthy.
Claims of responsibility and the official picture
Since 4 November, claim texts have circulated that name NoName057(16) and Z-Pentest; Telegram channels were reportedly deleted, and independent confirmation is missing (Cybernews). On 5 November the BSI told CORRECTIV that it had no evidence supporting such attributions; copycats were possible. The BSI said it was aware of individual incidents at supermarkets and in the pharmaceutical sector, and that the attacks appear untargeted and opportunistic (CORRECTIV). For your risk assessment, what matters is whether your devices are reachable, whoever stands behind the attacks.
Who is responsible for the controller
In many businesses an external refrigeration firm installs and maintains the system. The IT department knows the corporate network but often has no complete view of extra controllers and remote-maintenance routers. The refrigeration technician knows the plant but is not necessarily specialized in IT security. The operator expects the cooling to work. The result is a situation in which several parties keep the operation running and no one consistently owns the digital attack surface.
This especially affects smaller stores, restaurants and businesses without their own OT security team. They do not have to administer the technology themselves. They should, however, be able to demand solid answers from their contractors: Is the controller reachable directly from the internet? Who holds administrative credentials? How are security updates applied? What access do third parties have? Who is notified when a setpoint or defrost program leaves the intended operating range? Anyone who offers remote maintenance must be able to explain how that access is protected. Responsibility for secure operation does not end with the installation contract.
What to do by Monday
- Inventory refrigeration, HVAC and building controllers that have a web interface. Manufacturer, firmware, who operates remote access, whether a public IP or port forward exists.
- Remove public reachability. Remote maintenance only via VPN or a centrally managed maintenance solution with MFA, time limits and logging. IP filters limited to contractor addresses, as CERT-FR notes, only as an emergency measure.
- Firmware and passwords. Danfoss AK-SM 8xxA at least 4.3.1, security mode “Strict”, no default passwords. That release closes the three flaws now in KEV and CVE-2025-41451. Copeland/Dixell XWEB Pro on 1.13. If a controller was reachable from the internet, we check before or with the update whether it has been compromised. Isolate or replace EOL devices; a factory reset alone is not enough if the firmware remains exposed and unpatched (CERT-FR).
- Check the configuration. Defrost times, setpoints, alarm destinations; document deviations.
- Network and permissions. Controllers in their own segment, separate from office IT; contractors only on the devices they need; monitoring without write access where possible.
- Independent alerting for critical cold chains: sensors and a notification path outside the attacked controller.